Back to HVAC/R Toolkit
    HVAC/R Toolkit

    Boiler Fault Codes

    Condensing, fire-tube, water-tube, combi boiler and burner-management codes for Lochinvar, Weil-McLain, Cleaver-Brooks, Fulton, AERCO, Viessmann, Honeywell, Fireye, Siemens, and more.

    Boiler Fault Codes

    Fire-tube, water-tube, condensing, and combi boiler diagnostics plus burner-management codes for Lochinvar, Weil-McLain, Cleaver-Brooks, Fulton, AERCO, Viessmann, Honeywell, Fireye, Siemens, and more.

    Coverage
    667codes
    18 controllers across 18 brands
    Filter by brand / controller
    Browsing all 667 codes · page 1 of 14
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Ignition Failure Ignition Failure / No Flame Established
    Lockout — Manual Reset

    Boiler attempted to ignite but did not detect a flame within the trial-for-ignition period.

    Likely Causes
    • Gas supply off or low pressure
    • Faulty igniter or igniter cable
    • Dirty or failed flame sensor
    • Gas valve not opening
    First Checks
    • Verify gas supply valve is open
    • Check gas supply pressure (4-14" w.c. NG, 8-14" LP)
    • Inspect igniter for damage or debris
    • Test flame sensor rod continuity
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; lochinvar_boiler_trouble_codes.pdf (wsimg.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Flame Loss Flame Loss During Run
    Lockout — Manual Reset

    Flame was established but was lost during normal operation.

    Likely Causes
    • Gas pressure fluctuation
    • Dirty or failing flame sensor
    • Draft problem causing flame out
    • Gas valve failing
    First Checks
    • Check gas pressure stability during operation
    • Clean or replace flame sensor rod
    • Inspect venting for blockage or backdraft
    • Check gas valve operation
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    High Limit High Water Temperature Limit
    Lockout — Manual Reset

    Boiler outlet water temperature exceeded the high-limit setting (typically 210°F). Manual reset required.

    Likely Causes
    • Low or no water flow through boiler
    • Closed or failed zone valve
    • Failed pump
    • Scaled heat exchanger
    First Checks
    • Verify boiler pump operation on call for heat
    • Check system for closed valves
    • Confirm system is full of water and air-purged
    • Measure delta-T across boiler
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Gas Pressure SW Gas Pressure Switch Fault
    Lockout — Manual Reset

    Optional manual-reset low or high gas pressure switch has tripped. Manual reset required after correcting condition.

    Likely Causes
    • Gas supply pressure too low (<4" w.c. NG)
    • Gas supply pressure too high (>14" w.c. NG)
    • Missing jumper if switches not installed
    • Loose wiring at Low Voltage Connection Board
    First Checks
    • Reset pressure switches after correcting pressure
    • Measure supply gas pressure
    • Check for loose/missing jumper on Low Voltage Connection Board
    • Verify no additional device wired across gas pressure switch terminals
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; lochinvar_boiler_trouble_codes.pdf
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Flow Switch/LWCO Flow Switch / Low Water Cutoff Fault
    Lockout — Manual Reset

    Optional flow switch or low water cutoff device is open. Manual reset required after correcting condition.

    Likely Causes
    • Pump not running
    • Closed valve or obstruction in piping
    • System low on water
    • Air in system
    • Blown fuse F3 on control board
    First Checks
    • Check boiler pump operation on call for heat
    • Check for closed valves or obstructions
    • Verify system is full of water and air has been purged
    • Replace fuse F3 on control board if blown
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; lochinvar_boiler_trouble_codes.pdf
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Blocked Drain SW Blocked Drain Switch / Condensate Backup
    Lockout — Manual Reset

    Blocked drain switch detected excessive condensate buildup inside the unit. Manual reset required.

    Likely Causes
    • Condensate drain tube kinked or blocked
    • Condensate trap plugged
    • Loose wiring at drain switch harness
    • Failed blocked drain switch
    First Checks
    • Inspect condensate tube for obstructions
    • Inspect and clean condensate trap
    • Check wiring harness plug at drain switch
    • Replace blocked drain switch if faulty
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; lochinvar_boiler_trouble_codes.pdf
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Flue Temp High High Flue Temperature Lockout
    Lockout — Manual Reset

    Flue gas temperature exceeded maximum allowable limit. Indicates abnormal combustion or blocked heat exchanger.

    Likely Causes
    • Fouled or scaled heat exchanger
    • Incorrect gas valve calibration
    • Blocked flue sensor
    • Combustion tuning issue
    First Checks
    • Verify flue sensor location in flue outlet
    • Check heat exchanger for scale or debris
    • Review combustion analysis
    • Check flue sensor wiring
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; Crest Modbus Register List (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Air Pressure SW Air / Flue Pressure Switch Fault
    Lockout — Manual Reset

    Combustion air proving switch or blocked flue switch did not make within the expected time frame.

    Likely Causes
    • Blocked air intake or flue
    • Failed or sticky pressure switch
    • Loose tubing to pressure switch
    • Failed combustion blower
    First Checks
    • Inspect air intake and flue for blockage (ice, debris)
    • Verify combustion blower starts and runs to speed
    • Check pressure switch tubing for cracks
    • Test pressure switch with manometer
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; combiboiler.ca/lochinvar
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Blower Fault Combustion Blower Fault
    Lockout — Manual Reset

    Combustion blower (fan) did not reach commanded speed within the expected time, or lost speed during operation.

    Likely Causes
    • Failed blower motor
    • Blower obstructed
    • Blower control board fault
    • Wiring failure to blower
    First Checks
    • Listen for blower startup; verify it reaches speed
    • Inspect blower wheel for debris or damage
    • Check 120VAC supply to blower
    • Check wiring harness from control board to blower
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; combiboiler.ca/lochinvar
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Gas Valve Fault Gas Valve Circuit / Modulation Fault
    Lockout — Manual Reset

    Gas valve circuit fault — modulating valve cannot reach commanded position, or a wiring fault exists.

    Likely Causes
    • Failed gas valve
    • Broken or shorted gas valve wiring
    • Main control board output failure
    • Gas valve coil failure
    First Checks
    • Check 24VAC at gas valve terminals on call for heat
    • Inspect gas valve wiring harness for damage
    • Verify gas valve resistance per service manual
    • Replace gas valve if coil open or shorted
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C; combiboiler.ca/lochinvar
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Supply Sensor Fault Outlet (Supply) Temperature Sensor Fault
    Shutdown

    Outlet water temperature sensor is reading out of range (open or short circuit).

    Likely Causes
    • Sensor connector loose or disconnected
    • Damaged sensor cable
    • Failed NTC temperature sensor
    • Water ingress in sensor pocket
    First Checks
    • Check wiring connector at sensor
    • Measure sensor resistance and compare to chart in service manual
    • Inspect sensor for physical damage
    • Replace sensor if resistance out of range
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Return Sensor Fault Return Water Temperature Sensor Fault
    Shutdown

    Return (inlet) water temperature sensor is reading out of range.

    Likely Causes
    • Sensor connector loose
    • Damaged sensor cable
    • Failed NTC sensor
    • Sensor installed incorrectly
    First Checks
    • Check wiring at sensor connector
    • Measure sensor resistance vs. chart (Table 3-2)
    • Inspect sensor for physical damage
    • Replace sensor
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Flue Sensor Fault Flue Temperature Sensor Fault
    Shutdown

    Flue temperature sensor is open or reading out of range.

    Likely Causes
    • Sensor not installed in flue outlet
    • Sensor wiring disconnected
    • Failed sensor
    • Sensor cable damage from high flue temp
    First Checks
    • Verify sensor is physically located in the flue outlet
    • Check wiring connections at sensor
    • Measure sensor resistance and compare to spec
    • Replace sensor if faulty
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Outdoor Sensor Fault Outdoor Temperature Sensor Fault
    Warning

    Outdoor reset sensor is open or out of range. Boiler will operate without outdoor reset until corrected.

    Likely Causes
    • Sensor lead broken by weather or UV exposure
    • Connector disconnected at control board
    • Failed sensor
    • Sensor location shielded from outdoor air
    First Checks
    • Inspect outdoor sensor cable for damage
    • Check connector at main control board
    • Measure sensor resistance at various outdoor temps
    • Replace sensor if faulty
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Cascade Comm Fault Cascade / BMS Communication Fault
    Warning

    Communication lost between cascaded boilers or between the boiler and a Building Management System (BMS).

    Likely Causes
    • BMS communication cable disconnected or broken
    • Incorrect Modbus/BACnet configuration
    • Incorrect slave ID or baud rate
    • Termination resistor missing
    First Checks
    • Check physical Modbus/BACnet cable connections
    • Verify dip switch configuration on MTR-01 board
    • Confirm baud rate and slave ID match BMS settings
    • Check for 120-ohm terminating resistors at ends of network
    Source: Lochinvar Crest Modbus Register List (ccontrols.com); lochinvar_error_codes.pdf
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-01 Blocking: Space Heating Demand Blocked
    Information

    Space heating demand blocked by the control (WWSD active or BMS command).

    Likely Causes
    • Warm weather shutdown (WWSD) active
    • Outdoor air temp above WWSD setpoint
    • BMS command to block SH
    • Cascade leader is blocking
    First Checks
    • Check WWSD setpoint vs. current outdoor temperature
    • Review BMS command to boiler
    • Check outdoor air sensor reading
    • Verify cascade leader status
    Source: Lochinvar Crest Modbus Register List, blocking code 1 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-02 Blocking: Low 24VAC Supply
    Shutdown

    24VAC control voltage is below minimum threshold; boiler blocked from starting.

    Likely Causes
    • Transformer undersized or failing
    • Excessive external load on 24V circuit
    • Wiring fault creating voltage drop
    • Transformer primary voltage low
    First Checks
    • Measure 24VAC at control board
    • Check for additional devices on 24V circuit
    • Inspect transformer output
    • Verify supply voltage to boiler
    Source: Lochinvar Crest Modbus Register List, blocking code 2 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-04 Blocking: MRHL Open (Manual Reset High Limit)
    Lockout — Manual Reset

    Manual reset high limit switch is open. Boiler will not fire until switch is manually reset.

    Likely Causes
    • High temperature event previously occurred
    • Wiring to limit switch open
    • Failed manual reset limit switch
    • Jumper missing if limit not installed
    First Checks
    • Identify and correct cause of previous high-temp event
    • Press reset button on manual reset high limit
    • Check wiring continuity to limit switch
    • Replace limit switch if faulty
    Source: Lochinvar Crest Modbus Register List, blocking code 4 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-07 Blocking: High Delta-T (Outlet-Inlet)
    Warning

    Temperature differential between boiler outlet and inlet exceeds maximum allowed value. Firing rate is being limited.

    Likely Causes
    • Low system flow rate
    • Air locked in system
    • Closed zone valves
    • Undersized pump
    First Checks
    • Verify pump is running and at correct speed
    • Check all zone valves are open
    • Purge air from system
    • Measure actual supply/return temperatures
    Source: Lochinvar Crest Modbus Register List, blocking code 7 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-08 Blocking: High Flue Temperature
    Warning

    Flue temperature is elevated; controller is limiting maximum firing rate.

    Likely Causes
    • Scale or fouling on heat exchanger
    • Combustion tuning too rich
    • Flue sensor malfunction
    • Restricted flue
    First Checks
    • Check heat exchanger for scale buildup
    • Review combustion analysis
    • Inspect flue for partial blockage
    • Verify flue sensor reading accuracy
    Source: Lochinvar Crest Modbus Register List, blocking code 8 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-14 Blocking: DHW Tank Demand Blocked (Fan Problems)
    Shutdown

    DHW tank demand blocked because combustion fan has reported a problem.

    Likely Causes
    • Fan motor fault
    • Fan speed sensor failure
    • Fan obstructed
    • Fan control signal wiring fault
    First Checks
    • Listen and confirm fan spins up on demand
    • Check fan speed feedback wire
    • Inspect fan inlet for obstruction
    • Measure voltage supply to fan motor
    Source: Lochinvar Crest Modbus Register List, blocking code 14 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-16 Blocking: Outlet Temperature Limit
    Warning

    Boiler outlet water temperature has reached the set limit; firing rate is reduced or blocked.

    Likely Causes
    • Setpoint too close to limit
    • Low flow causing rapid temp rise
    • Demand setpoint higher than design
    • Sensor reading high
    First Checks
    • Compare current outlet temp to limit setting
    • Check flow rate through boiler
    • Review temperature setpoint programming
    • Verify sensor accuracy
    Source: Lochinvar Crest Modbus Register List, blocking code 16 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-24 Blocking: High Temperature Rise
    Warning

    Temperature rise from inlet to outlet is exceeding allowable rate. Firing rate is being capped.

    Likely Causes
    • Low flow rate causing high delta-T
    • Bypass valve stuck closed
    • Air-locked system
    • Pump failure
    First Checks
    • Verify pump is operational
    • Check for air in system
    • Inspect bypass valve if installed
    • Measure actual inlet and outlet temperatures
    Source: Lochinvar Crest Modbus Register List, blocking code 24 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-26 Blocking: High Outlet Water Temperature
    Shutdown

    Outlet water temperature exceeds software high-limit setpoint, preventing firing.

    Likely Causes
    • Setpoint too low relative to actual load
    • Sensor offset error
    • High-limit set too close to operating setpoint
    • Demand calling unexpectedly
    First Checks
    • Review high-limit setpoint in SMART SYSTEM parameters
    • Check temperature sensor accuracy
    • Verify demand type and source
    • Allow boiler to cool before restart
    Source: Lochinvar Crest Modbus Register List, blocking code 26 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Block-27 Blocking: Anti-Cycling Time Active
    Information

    Boiler is in anti-cycling delay period and will not restart until the delay has elapsed.

    Likely Causes
    • Normal operation after recent shutdown
    • Oversized boiler for load
    • Short-cycling load profile
    First Checks
    • Wait for anti-cycling delay to expire
    • Review boiler sizing for the load
    • Check minimum off-time setting in parameters
    Source: Lochinvar Crest Modbus Register List, blocking code 27 (ccontrols.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Low Water Low Water Pressure / Low Water Cutoff
    Shutdown

    System water pressure is below minimum threshold or the low-water cutoff device has opened.

    Likely Causes
    • System pressure below 10 PSI
    • Leak in system
    • Expansion tank waterlogged or failed
    • Fill valve not maintaining pressure
    First Checks
    • Check system pressure gauge (should be 12-15 PSI cold)
    • Inspect system for water leaks
    • Check expansion tank pre-charge
    • Verify automatic fill valve operation
    Source: Lochinvar FTXL User Manual 100361312; combiboiler.ca/lochinvar
    Lochinvar · SMART SYSTEM / SMART TOUCH
    O-Temp HEX Over-Temperature Heat Exchanger Switch
    Lockout — Manual Reset

    Thermal fuse or over-temperature switch on the heat exchanger body has opened, indicating extreme localized temperature.

    Likely Causes
    • No water flow through heat exchanger
    • Scale buildup causing hot spots
    • Failed thermal fuse
    • Fire from previous ignition fault
    First Checks
    • Restore water flow before attempting reset
    • Check heat exchanger for scale
    • Test thermal switch/fuse continuity
    • Replace thermal fuse if blown
    Source: Lochinvar Knight XL Service Manual KBXII-SER Rev C (O-temp HEX switch added Rev C)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Stack Temp Limit Stack Temperature High Limit (Power-Fin)
    Lockout — Manual Reset

    Stack (flue gas) temperature has exceeded the high-limit setting on the Power-Fin boiler.

    Likely Causes
    • Scale or fouling in heat exchanger
    • Incorrect combustion air/fuel ratio
    • Flue gas bypass damper open
    • Failed stack sensor
    First Checks
    • Read actual stack temperature from display
    • Inspect heat exchanger for deposits
    • Perform combustion analysis
    • Verify stack temperature sensor operation
    Source: Lochinvar Power-Fin Service Manual 596898100280636_2000538993 Rev H (lochinvar.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Inlet Temp High High Inlet Water Temperature
    Shutdown

    Inlet water temperature to the boiler exceeds maximum allowed value, preventing firing to avoid thermal shock.

    Likely Causes
    • Return water from system too hot (>180°F)
    • System mixing valve failed
    • Pipe crossover between supply and return
    • Heat stored in large volume system
    First Checks
    • Measure actual inlet temperature
    • Check for hydraulic short circuit
    • Verify mixing valve is operating correctly
    • Review piping diagram for cross-connections
    Source: Lochinvar Power-Fin Service Manual 596898100280636_2000538993 Rev H
    Lochinvar · SMART SYSTEM / SMART TOUCH
    System Sensor Fault System Header Sensor Fault
    Warning

    Header or system sensor (cascade/modular systems) is open or out of range.

    Likely Causes
    • Sensor disconnected from header well
    • Sensor wiring damage
    • Failed sensor
    • Incorrect sensor type installed
    First Checks
    • Check sensor physically seated in well
    • Inspect wiring back to control board
    • Measure resistance and compare to spec
    • Replace sensor if out of tolerance
    Source: Lochinvar Crest Modbus Register List (ccontrols.com); blocking code 15
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Waterside Pressure Waterside Pressure Fault (FTXL)
    Shutdown

    FTXL fire tube boiler detected low system water pressure below minimum operating pressure.

    Likely Causes
    • System pressure below 10 PSI
    • Leak in system
    • Fill valve failure
    • Expansion tank failure
    First Checks
    • Check pressure at boiler gauge
    • Inspect system for leaks
    • Check expansion tank
    • Verify automatic fill valve operation
    Source: Lochinvar FTXL User Manual 100361312_2000617081 Rev A (lochinvar.com)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    Service Due Service Due Notification
    Information

    Annual service reminder has triggered. Boiler continues to operate but service is needed.

    Likely Causes
    • Service interval timer elapsed (typically 12 months)
    • First startup notification not cleared
    First Checks
    • Perform annual service and reset service notification from SMART SYSTEM menu
    • Follow procedure shown in YouTube video eblTFsymZb0 for reset
    Source: Lochinvar Knight SMART SYSTEM service notification (YouTube: eblTFsymZb0)
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E119 Low Gas Pressure During Run
    Shutdown

    Gas pressure dropped below minimum during firing

    Likely Causes
    • Gas supply pressure dropped during firing
    • Gas regulator undersized for demand
    • Competing appliances drawing gas
    First Checks
    • Monitor gas pressure during operation
    • Check gas regulator size and setting
    • Verify no other appliances are consuming gas
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E128 Stack Temperature Too High
    Lockout — Manual Reset

    Stack gas temperature exceeded maximum allowable limit

    Likely Causes
    • Fouled heat exchanger surfaces
    • Recirculation of flue gases
    • Excessive input rate
    First Checks
    • Clean heat exchanger flue passages
    • Inspect venting for recirculation
    • Verify input rate setting
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E130 Ignition Failure — Trial 3
    Lockout — Manual Reset

    Third ignition trial failure — manual reset lockout

    Likely Causes
    • Gas supply problems
    • Igniter electrode worn or fouled
    • Gas valve malfunction
    • Defective ignition transformer
    First Checks
    • Check gas supply and pressure
    • Inspect igniter electrode
    • Test gas valve
    • Check ignition transformer output
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E149 DHW Outlet Sensor Fault
    Warning

    DHW outlet temperature sensor open or short circuit

    Likely Causes
    • DHW outlet sensor wiring fault
    • Defective sensor
    • Loose connector
    First Checks
    • Check DHW outlet sensor wiring
    • Measure sensor resistance
    • Replace sensor
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E152 DHW Inlet Sensor Fault
    Warning

    DHW inlet temperature sensor open or short circuit

    Likely Causes
    • DHW inlet sensor wiring fault
    • Defective sensor
    First Checks
    • Check DHW inlet sensor wiring
    • Measure sensor resistance
    • Replace sensor
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E162 Fan Speed Low During Run
    Shutdown

    Fan speed dropped below minimum during firing

    Likely Causes
    • Fan motor wear or failure
    • Restriction in air intake or flue
    • Fan speed control issue
    First Checks
    • Check fan speed during firing
    • Inspect air inlet and flue for restriction
    • Test fan motor
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E164 Condensate System Fault
    Warning

    Condensate system fault detected — blocked drain or backup

    Likely Causes
    • Blocked condensate drain
    • Frozen condensate trap
    • Condensate neutralizer clogged
    First Checks
    • Check condensate drain for blockage
    • Inspect condensate trap and neutralizer
    • Check drain line slope
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E195 Low Water Cutoff Active
    Lockout — Manual Reset

    Low water cutoff device has activated

    Likely Causes
    • System water level below minimum
    • Air in system causing false LWCO trigger
    • Defective LWCO device
    First Checks
    • Check system water level and add water if needed
    • Bleed air from system
    • Test LWCO device operation
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E211 Header Sensor Fault
    Warning

    Header temperature sensor open or short circuit

    Likely Causes
    • Header sensor wiring fault
    • Defective header sensor
    First Checks
    • Check header sensor wiring
    • Measure resistance
    • Replace sensor
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E214 High Limit Circuit Open
    Lockout — Manual Reset

    External high limit circuit is open

    Likely Causes
    • Manual-reset high limit tripped
    • External safety device open
    • Missing wiring jumper
    First Checks
    • Check and manually reset high limit switch
    • Inspect external safety devices
    • Verify jumper if no external device
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E215 Auxiliary Sensor 1 Fault
    Warning

    Auxiliary sensor 1 open or short circuit

    Likely Causes
    • Auxiliary sensor 1 wiring fault
    • Defective sensor
    First Checks
    • Check aux sensor 1 wiring
    • Measure resistance
    • Replace sensor
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E217 Outdoor Temperature Sensor Fault
    Warning

    Outdoor air temperature sensor open or short circuit

    Likely Causes
    • Outdoor sensor wiring damaged or exposed to weather
    • Defective sensor
    • Connector corrosion
    First Checks
    • Inspect outdoor sensor wiring for weather damage
    • Measure sensor resistance
    • Replace sensor and protect from weather
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E310 BST Communication Fault
    Warning

    Boiler sequencing communication fault

    Likely Causes
    • BST network cable disconnected or damaged
    • Address conflict on BST network
    • Power loss to one or more BST boilers
    First Checks
    • Check BST network cabling between boilers
    • Verify boiler addresses are unique
    • Check all BST boilers are powered
    Lochinvar · SMART SYSTEM / SMART TOUCH
    E316 Modbus Communication Fault
    Warning

    Modbus communication fault

    Likely Causes
    • Modbus wiring fault
    • Incorrect Modbus address or baud rate settings
    • BAS not communicating
    First Checks
    • Check Modbus RS-485 wiring
    • Verify Modbus address and communication settings
    • Test BAS connection
    Weil-McLain · Ultra/Evergreen Sage control, GV90+ integrated control, Aqua-Plus/AquaBalance controller
    E01 Outlet High Temperature — Lockout
    Lockout — Manual Reset

    Boiler outlet water temperature exceeded the high-limit value; boiler has locked out.

    Likely Causes
    • Low or no water circulation
    • Closed zone valve or pump failure
    • Air-locked system
    • Scale in heat exchanger
    First Checks
    • Verify pump is running
    • Check all zone valves for proper operation
    • Purge air from system
    • Measure actual outlet temperature
    Source: Weil-McLain Ultra Boiler Fault Codes PDF (img1.wsimg.com/d30153d6); heatland.ca/weil-mclain-boiler-error-codes
    Weil-McLain · Ultra/Evergreen Sage control, GV90+ integrated control, Aqua-Plus/AquaBalance controller
    E02 Inlet High Temperature — Lockout
    Lockout — Manual Reset

    Boiler inlet water temperature exceeded the high-inlet limit, indicating return water is too hot.

    Likely Causes
    • Hot water bypassing back to return
    • System hydraulic short-circuit
    • Heat stored in buffer tank returning too hot
    • Piping error
    First Checks
    • Check for hydraulic short circuit between supply and return
    • Measure actual inlet temperature
    • Review piping configuration
    • Verify mixing valve if installed
    Source: Weil-McLain Ultra Boiler Fault Codes PDF (img1.wsimg.com/d30153d6)
    Weil-McLain · Ultra/Evergreen Sage control, GV90+ integrated control, Aqua-Plus/AquaBalance controller
    E03 No Ignition — Lockout
    Lockout — Manual Reset

    Boiler failed to establish a flame on 3 consecutive ignition attempts.

    Likely Causes
    • Gas supply off or low pressure
    • Faulty igniter
    • Failed flame sensor
    • Gas valve not opening
    First Checks
    • Confirm gas supply is on and at correct pressure
    • Inspect igniter for damage
    • Test flame sensor
    • Check gas valve for operation
    Source: Weil-McLain Ultra Boiler Fault Codes PDF; heatland.ca/weil-mclain
    Weil-McLain · Ultra/Evergreen Sage control, GV90+ integrated control, Aqua-Plus/AquaBalance controller
    E04 Flame Lost During Operation — Lockout
    Lockout — Manual Reset

    Flame lost during normal operation (not during ignition trial).

    Likely Causes
    • Gas supply interruption
    • Combustion air issue
    • Draft problems
    • Failing flame sensor
    First Checks
    • Check gas pressure during operation
    • Inspect air supply and venting
    • Test flame sensor signal strength
    • Check venting for backdraft
    Source: Weil-McLain Ultra Boiler Fault Codes PDF (img1.wsimg.com/d30153d6)
    Page 1 of 14