Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
F0 , Starter Did Not Transition
Lockout, Manual Reset
Transition-complete signal not received within 2.5 s of transition command. Y-delta, autotransformer, primary reactor, X-line starters.
Likely Causes
Run contactor failed to close
Transition complete limit switch malfunction
Wiring fault on transition signal circuit
First Checks
Check transition complete wiring to UC800
Manually test run contactor operation
Verify contactor auxiliary contact continuity
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
1F5 , Compressor Did Not Accelerate Fully
Lockout, Manual Reset
SSS did not signal Up to Speed or End of Ramp within 2.5 s after commanding bypass, applies to SSS/AFD only.
Likely Causes
Excessive load at startup
Motor shaft binding or mechanical restriction
SSS ramp rate set too slow
First Checks
Check compressor for mechanical binding
Verify SSS acceleration time setpoint
Inspect motor for high temperature (recent overload)
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
EE , Compressor Did Not Accelerate: Shutdown
Lockout, Manual Reset
Motor did not reach <85% RLA within maximum acceleration timer, start aborted.
Likely Causes
Motor overloaded
Low supply voltage during start
Mechanical restriction in compressor
First Checks
Check supply voltage under load
Verify maximum acceleration timer setting
Inspect compressor for mechanical resistance
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
3D5 , Transition Complete Input Shorted
Lockout, Manual Reset
Transition complete input shorted before compressor start, wiring fault.
Likely Causes
Wiring short circuit on TC input
Defective auxiliary contact reporting closure
First Checks
Inspect wiring for short to ground or common
Test auxiliary contact with ohmmeter
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
3D6 , At Speed Input Shorted
Lockout, Manual Reset
At Speed input shorted before compressor start (SSS/AFD). Indicates wiring fault.
Likely Causes
Wiring short on At Speed signal
Defective SSS or AFD feedback contact
First Checks
Test At Speed feedback wiring for shorts
Verify SSS/AFD output contact
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
3D7 , Transition Complete Input Opened
Lockout, Manual Reset
Transition complete input opened while compressor running, contactor auxiliary contact dropped out.
Likely Causes
Run contactor dropped out unexpectedly
Auxiliary contact worn or intermittent
Loose wiring on TC input
First Checks
Check run contactor for premature dropout
Test auxiliary contact under running conditions
Inspect terminal tightness
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
3D8 , At Speed Input Opened
Lockout, Manual Reset
At Speed input opened while compressor running (SSS/AFD) after successful bypass.
Likely Causes
SSS or AFD At Speed output dropped mid-run
Intermittent wiring on At Speed signal
First Checks
Monitor SSS/AFD At Speed output during run
Check wiring and connections
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
EC , Motor Current Overload
Lockout, Manual Reset
Compressor current exceeded overload trip characteristic (must trip = 140% RLA, nominal trip at 132.5% in 30 s).
Likely Causes
Overloaded compressor from high differential pressure
Low supply voltage causing higher current draw
Motor bearing failure
Refrigerant overcharge
First Checks
Check condenser approach temperature and condenser water flow
Verify supply voltage at full load
Compare actual current to RLA nameplate
Check refrigerant charge
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
CA , Starter Contactor Interrupt Failure
Lockout, Manual Reset
Compressor current >10% RLA detected on any phase when compressor commanded off, contactor failed to open.
Likely Causes
Welded main contactor contacts
Shorted SCR in SSS
First Checks
Immediately check contactor for welded tips
Lock out and tag out, do not restart
Inspect SSS for shorted SCR
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
D7 , Over Voltage
Shutdown
Average line voltage exceeded +10% of nominal (nominal trip: 60 s at >112.5%). Auto-resets at 109% or less.
Likely Causes
Utility overvoltage condition
Failed voltage regulator on transformer
Tap setting on transformer too high
First Checks
Measure supply voltage at all three phases
Check transformer tap setting
Contact utility if voltage consistently high
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
D8 , Under Voltage
Shutdown
Average line voltage below -10% of nominal (nominal trip: 60 s at <87.5%). Auto-resets at 90% or greater.
Likely Causes
Utility undervoltage
Overloaded electrical panel
Loose main feed connection
Transformer tap set too low
First Checks
Measure supply voltage under full load
Check transformer tap setting
Inspect main feed terminals for heat or looseness
Contact utility
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
FB , Low Evaporator Refrigerant Temperature
Lockout, Manual Reset
Saturated evaporator refrigerant temperature (from suction pressure) dropped below Low Refrigerant Temperature Cutout (LRTC) setpoint for a 450°F-s integral.
Likely Causes
Loss of chilled water flow
Low load with LRTC setpoint too high
Refrigerant undercharge
Fouled evaporator tubes
First Checks
Verify evaporator water flow and differential pressure
Check chilled water pump operation
Confirm refrigerant charge
Check LRTC setpoint (min -5°F)
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
198 , Low Oil Flow
Lockout, Manual Reset
Oil pressure ratio (PC-Po)/(PC-PE) out of acceptable range for 15 s while differential pressure >15 psiD.
Likely Causes
Oil pump failure
Clogged oil filter
Low oil level
Oil cooler blockage
First Checks
Check oil differential pressure on service tool
Inspect oil filter condition
Verify oil level in sight glass
Check oil cooler for fouling
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
59C , Loss of Oil at Compressor (Running)
Lockout, Manual Reset
Oil loss level sensor detects lack of oil in the oil tank while compressor is running.
Likely Causes
Oil pump failure
Oil return line blockage
Low refrigerant charge causing oil migration
Eductor system not functioning
First Checks
Check oil level and sight glass while running
Inspect oil pump operation
Verify eductor operation
Check for refrigerant undercharge
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
59D , Loss of Oil at Compressor (Stopped)
Shutdown
Oil loss level sensor detects lack of oil 90 s after EXV preposition completed during pre-start. Start delayed.
Likely Causes
Insufficient oil in system
Oil migration during off-cycle
Oil pump not priming
First Checks
Verify oil level at pre-start
Add oil if below minimum
Check heater operation during off-cycle
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
1AE , Low Differential Refrigerant Pressure
Lockout, Manual Reset
System differential pressure (condenser-evaporator) below 15 psiD for >164 psiD-s, or below 23 psiD for >3000 psiD-s (non-volatile integral).
Likely Causes
Refrigerant leak
EXV stuck open flooding evaporator
Low load condition
Compressor valve failure
First Checks
Verify differential pressure on service tool
Check refrigerant charge
Inspect EXV operation
Check for refrigerant leaks
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
297 , No Differential Refrigerant Pressure
Lockout, Manual Reset
System differential pressure below 7.7 psiD, saturates the Low Diff Rfgt Press integral and invokes compressor cool-down mode.
Likely Causes
Major refrigerant leak
Flooded evaporator
Compressor not building head pressure
First Checks
Check for major refrigerant leak immediately
Inspect compressor operation
Verify condenser water flow
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
398 , BAS Communication Lost
Warning
BAS was configured as 'installed' at MP and Comm 3 LLID lost communications with BAS for 15 continuous minutes.
AFD on compressor 1A reports motor current overload condition.
Likely Causes
High differential pressure overloading compressor
Low supply voltage
Drive parameter mismatch
First Checks
Check condenser pressure and approach
Verify drive motor nameplate parameters
Check supply voltage
Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
Trane · Tracer UC800 / Tracer CH530
506 , AFD Motor Current Overload (Ckt 2A)
Lockout, Manual Reset
AFD on compressor 2A reports motor current overload, same criteria as code 504 for circuit 2.
Likely Causes
High differential pressure on circuit 2
Low voltage
Mechanical restriction on compressor 2A
First Checks
Check circuit 2 condenser pressure
Verify drive parameters for ckt 2
Inspect compressor 2A for binding
Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
Trane · Tracer UC800 / Tracer CH530
508 , AFD Interrupt Failure (Ckt 1A)
Lockout, Manual Reset
AFD interrupt signal failure on compressor 1A, internal drive communication failure.
Likely Causes
Drive control board failure
Noise on drive communication bus
Drive firmware issue
First Checks
Power-cycle the drive after lockout
Check drive for internal fault codes
Inspect drive control wiring for noise sources
Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
Trane · Tracer UC800 / Tracer CH530
D9 , MP Reset Has Occurred
Information
Main processor successfully came out of reset and rebuilt application (power-up, software install, or reconfiguration). Informational, auto-clears.
Likely Causes
Normal power-up
Software update applied
Watchdog-triggered reset
First Checks
Review historic diagnostic list for prior faults that caused reset
Confirm no other active diagnostics
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
6B5 , Unexpected Starter Shutdown
Warning
Starter module reported stopped when it should be running, and no starter diagnostic exists. Auto-logs and clears.
Likely Causes
Power transient caused brief starter dropout
Starter communication glitch
Loose starter signal wiring
First Checks
Review event history for frequency
Check starter signal wiring
Monitor supply voltage quality
Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
Trane · Tracer UC800 / Tracer CH530
CH530-LOCHW , Low Chilled Water Temperature
Shutdown
Leaving chilled water temperature dropped below the Low Chilled Water Temperature Cutout setpoint (typically 36–40°F for water; lower for glycol). Non-latching auto-reset.
Likely Causes
Low chilled water flow
Load turned off suddenly
Control setpoint set too close to low limit
Freeze protection activation
First Checks
Verify chilled water pump is running and flow is established
Condenser refrigerant pressure exceeded condenser pressure cutout setpoint (adaptive, typically 132 psiA for R-134a). Compressor unloads, then trips if not recovered.
Likely Causes
Insufficient condenser water flow
High condenser water entering temperature
Non-condensables in refrigerant
Fouled condenser tubes
First Checks
Verify condenser water flow and pump operation
Check cooling tower performance
Review condenser approach temperature
Check for non-condensables, purge unit if equipped