Back to HVAC/R Toolkit
    HVAC/R Toolkit

    Chiller Fault Codes

    Centrifugal and screw liquid chiller codes for Trane, Carrier, York / JCI, Daikin Applied, Climacool, and Multistack.

    Chiller Fault Codes

    Centrifugal and screw liquid chiller diagnostics for Trane, Carrier, York / Johnson Controls, Daikin Applied, Climacool, and Multistack.

    Coverage
    287codes
    8 controllers across 6 brands
    Filter by brand / controller
    Browsing all 287 codes · page 1 of 6
    Trane · Tracer UC800 / Tracer CH530
    E5 Phase Reversal
    Lockout — Manual Reset

    Reversed phase sequence detected on incoming power at compressor startup — must trip within 0.3 s.

    Likely Causes
    • Power supply wiring phased incorrectly
    • Utility power reversal after outage
    • Starter contactor wired out of sequence
    First Checks
    • Verify incoming phase sequence with a phase rotation meter
    • Check all power wiring connections at the starter terminals
    • Inspect for recent utility work or power restoration events
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    E4 Phase Loss
    Lockout — Manual Reset

    One or two phases of compressor current lost while running or starting; trip at <10% RLA for 2.64 s.

    Likely Causes
    • Blown fuse on one phase
    • Open contactor contact
    • Loose power terminal
    • Utility single-phasing
    First Checks
    • Check all three fuses at the motor disconnect
    • Verify current on all three phases with a clamp meter
    • Inspect contactor contacts for burning or pitting
    • Tighten all power terminal connections
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    E2 Momentary Power Loss
    Shutdown

    Loss of power for three or more line cycles detected (MPL option must be enabled). Auto-resets in 30 s.

    Likely Causes
    • Utility voltage sag or brief outage
    • Loose incoming power connection
    • Overloaded electrical distribution
    First Checks
    • Check utility voltage logs or power quality meter
    • Inspect incoming connection tightness
    • Review chiller event history for frequency of occurrence
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1A0 Power Loss
    Shutdown

    All three phases of compressor current lost while running (previously established). Auto-resets in 10 s.

    Likely Causes
    • Complete power interruption
    • Utility outage
    • Main breaker trip
    First Checks
    • Confirm utility power restoration
    • Reset main breaker if tripped
    • Check for nuisance MPL if recurring
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    E3 Severe Current Imbalance
    Lockout — Manual Reset

    30% current imbalance on one phase relative to 3-phase average sustained for 90 continuous seconds.

    Likely Causes
    • Unbalanced utility supply voltage
    • Single weak contactor contact
    • Motor winding beginning to fail
    First Checks
    • Measure and compare all three line voltages
    • Check contactors for wear
    • Log all three phase currents during run
    • Notify utility if supply imbalance exceeds 2%
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1E9 Starter Fault Type I
    Lockout — Manual Reset

    Current detected on CTs when only the 1M (1K1) main contactor is closed at start — indicates shorted secondary contactor. Y-delta starters only.

    Likely Causes
    • Shorted run contactor
    • Wiring fault between contactors
    First Checks
    • Inspect all starter contactors for welded contacts
    • Verify wiring per starter schematic
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1ED Starter Fault Type II
    Lockout — Manual Reset

    Current detected on CTs when only shorting contactor (1K3) is energized — indicates shorted 1M contactor.

    Likely Causes
    • Welded main contactor (1M/1K1)
    • Wiring cross-fault
    First Checks
    • Check 1M contactor for welded tips
    • Inspect wiring for shorts
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1F1 Starter Fault Type III
    Lockout — Manual Reset

    No CT current 1.6 s after both shorting and main contactors energized — motor not responding to start command.

    Likely Causes
    • Open motor winding
    • Blown fuse after contactor
    • Motor terminal disconnect loose
    First Checks
    • Verify power at motor terminals under load
    • Meg-ohm test motor windings
    • Check post-contactor fusing
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    189 Solid State Starter Fault
    Lockout — Manual Reset

    Solid State Starter (SSS) fault relay opened — internal SSS protection activated.

    Likely Causes
    • SSS internal overload
    • SCR device failure
    • Communication fault between SSS and UC800
    First Checks
    • Read SSS local fault display or LED indicators
    • Check SSS-to-UC800 signal wiring
    • Verify SSS power supply
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    701 AFD Drive Fault
    Lockout — Manual Reset

    Adaptive Frequency Drive (AFD) fault relay opened — internal VFD protection triggered.

    Likely Causes
    • VFD internal fault (overcurrent, overvoltage, overtemperature)
    • VFD-to-UC800 communication loss
    • Drive cooling fan failure
    First Checks
    • Read drive keypad fault code
    • Check drive cooling airflow and filter
    • Verify DC bus voltage within spec
    • Check drive-to-controller communication cable
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    F0 Starter Did Not Transition
    Lockout — Manual Reset

    Transition-complete signal not received within 2.5 s of transition command. Y-delta, autotransformer, primary reactor, X-line starters.

    Likely Causes
    • Run contactor failed to close
    • Transition complete limit switch malfunction
    • Wiring fault on transition signal circuit
    First Checks
    • Check transition complete wiring to UC800
    • Manually test run contactor operation
    • Verify contactor auxiliary contact continuity
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1F5 Compressor Did Not Accelerate Fully
    Lockout — Manual Reset

    SSS did not signal Up to Speed or End of Ramp within 2.5 s after commanding bypass — applies to SSS/AFD only.

    Likely Causes
    • Excessive load at startup
    • Motor shaft binding or mechanical restriction
    • SSS ramp rate set too slow
    First Checks
    • Check compressor for mechanical binding
    • Verify SSS acceleration time setpoint
    • Inspect motor for high temperature (recent overload)
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    EE Compressor Did Not Accelerate: Shutdown
    Lockout — Manual Reset

    Motor did not reach <85% RLA within maximum acceleration timer — start aborted.

    Likely Causes
    • Motor overloaded
    • Low supply voltage during start
    • Mechanical restriction in compressor
    First Checks
    • Check supply voltage under load
    • Verify maximum acceleration timer setting
    • Inspect compressor for mechanical resistance
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    3D5 Transition Complete Input Shorted
    Lockout — Manual Reset

    Transition complete input shorted before compressor start — wiring fault.

    Likely Causes
    • Wiring short circuit on TC input
    • Defective auxiliary contact reporting closure
    First Checks
    • Inspect wiring for short to ground or common
    • Test auxiliary contact with ohmmeter
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    3D6 At Speed Input Shorted
    Lockout — Manual Reset

    At Speed input shorted before compressor start (SSS/AFD). Indicates wiring fault.

    Likely Causes
    • Wiring short on At Speed signal
    • Defective SSS or AFD feedback contact
    First Checks
    • Test At Speed feedback wiring for shorts
    • Verify SSS/AFD output contact
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    3D7 Transition Complete Input Opened
    Lockout — Manual Reset

    Transition complete input opened while compressor running — contactor auxiliary contact dropped out.

    Likely Causes
    • Run contactor dropped out unexpectedly
    • Auxiliary contact worn or intermittent
    • Loose wiring on TC input
    First Checks
    • Check run contactor for premature dropout
    • Test auxiliary contact under running conditions
    • Inspect terminal tightness
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    3D8 At Speed Input Opened
    Lockout — Manual Reset

    At Speed input opened while compressor running (SSS/AFD) after successful bypass.

    Likely Causes
    • SSS or AFD At Speed output dropped mid-run
    • Intermittent wiring on At Speed signal
    First Checks
    • Monitor SSS/AFD At Speed output during run
    • Check wiring and connections
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    EC Motor Current Overload
    Lockout — Manual Reset

    Compressor current exceeded overload trip characteristic (must trip = 140% RLA, nominal trip at 132.5% in 30 s).

    Likely Causes
    • Overloaded compressor from high differential pressure
    • Low supply voltage causing higher current draw
    • Motor bearing failure
    • Refrigerant overcharge
    First Checks
    • Check condenser approach temperature and condenser water flow
    • Verify supply voltage at full load
    • Compare actual current to RLA nameplate
    • Check refrigerant charge
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    CA Starter Contactor Interrupt Failure
    Lockout — Manual Reset

    Compressor current >10% RLA detected on any phase when compressor commanded off — contactor failed to open.

    Likely Causes
    • Welded main contactor contacts
    • Shorted SCR in SSS
    First Checks
    • Immediately check contactor for welded tips
    • Lock out and tag out — do not restart
    • Inspect SSS for shorted SCR
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    D7 Over Voltage
    Shutdown

    Average line voltage exceeded +10% of nominal (nominal trip: 60 s at >112.5%). Auto-resets at 109% or less.

    Likely Causes
    • Utility overvoltage condition
    • Failed voltage regulator on transformer
    • Tap setting on transformer too high
    First Checks
    • Measure supply voltage at all three phases
    • Check transformer tap setting
    • Contact utility if voltage consistently high
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    D8 Under Voltage
    Shutdown

    Average line voltage below -10% of nominal (nominal trip: 60 s at <87.5%). Auto-resets at 90% or greater.

    Likely Causes
    • Utility undervoltage
    • Overloaded electrical panel
    • Loose main feed connection
    • Transformer tap set too low
    First Checks
    • Measure supply voltage under full load
    • Check transformer tap setting
    • Inspect main feed terminals for heat or looseness
    • Contact utility
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    FB Low Evaporator Refrigerant Temperature
    Lockout — Manual Reset

    Saturated evaporator refrigerant temperature (from suction pressure) dropped below Low Refrigerant Temperature Cutout (LRTC) setpoint for a 450°F-s integral.

    Likely Causes
    • Loss of chilled water flow
    • Low load with LRTC setpoint too high
    • Refrigerant undercharge
    • Fouled evaporator tubes
    First Checks
    • Verify evaporator water flow and differential pressure
    • Check chilled water pump operation
    • Confirm refrigerant charge
    • Check LRTC setpoint (min -5°F)
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    198 Low Oil Flow
    Lockout — Manual Reset

    Oil pressure ratio (PC-Po)/(PC-PE) out of acceptable range for 15 s while differential pressure >15 psiD.

    Likely Causes
    • Oil pump failure
    • Clogged oil filter
    • Low oil level
    • Oil cooler blockage
    First Checks
    • Check oil differential pressure on service tool
    • Inspect oil filter condition
    • Verify oil level in sight glass
    • Check oil cooler for fouling
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    59C Loss of Oil at Compressor (Running)
    Lockout — Manual Reset

    Oil loss level sensor detects lack of oil in the oil tank while compressor is running.

    Likely Causes
    • Oil pump failure
    • Oil return line blockage
    • Low refrigerant charge causing oil migration
    • Eductor system not functioning
    First Checks
    • Check oil level and sight glass while running
    • Inspect oil pump operation
    • Verify eductor operation
    • Check for refrigerant undercharge
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    59D Loss of Oil at Compressor (Stopped)
    Shutdown

    Oil loss level sensor detects lack of oil 90 s after EXV preposition completed during pre-start. Start delayed.

    Likely Causes
    • Insufficient oil in system
    • Oil migration during off-cycle
    • Oil pump not priming
    First Checks
    • Verify oil level at pre-start
    • Add oil if below minimum
    • Check heater operation during off-cycle
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    1AE Low Differential Refrigerant Pressure
    Lockout — Manual Reset

    System differential pressure (condenser-evaporator) below 15 psiD for >164 psiD-s, or below 23 psiD for >3000 psiD-s (non-volatile integral).

    Likely Causes
    • Refrigerant leak
    • EXV stuck open flooding evaporator
    • Low load condition
    • Compressor valve failure
    First Checks
    • Verify differential pressure on service tool
    • Check refrigerant charge
    • Inspect EXV operation
    • Check for refrigerant leaks
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    297 No Differential Refrigerant Pressure
    Lockout — Manual Reset

    System differential pressure below 7.7 psiD — saturates the Low Diff Rfgt Press integral and invokes compressor cool-down mode.

    Likely Causes
    • Major refrigerant leak
    • Flooded evaporator
    • Compressor not building head pressure
    First Checks
    • Check for major refrigerant leak immediately
    • Inspect compressor operation
    • Verify condenser water flow
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    398 BAS Communication Lost
    Warning

    BAS was configured as 'installed' at MP and Comm 3 LLID lost communications with BAS for 15 continuous minutes.

    Likely Causes
    • BACnet/Modbus network cable fault
    • BAS controller offline
    • Communication module (LLID) failure
    • Incorrect address or baud rate
    First Checks
    • Check BAS network wiring and terminations
    • Verify BAS controller is online
    • Confirm Comm 3 LLID LED status
    • Verify communication parameters match BAS
    Source: acerrorcode.com citing Trane CH530 UC800 diagnostics; Trane RLC-SVU006B-GB
    Trane · Tracer UC800 / Tracer CH530
    504 AFD Motor Current Overload (Ckt 1A)
    Lockout — Manual Reset

    AFD on compressor 1A reports motor current overload condition.

    Likely Causes
    • High differential pressure overloading compressor
    • Low supply voltage
    • Drive parameter mismatch
    First Checks
    • Check condenser pressure and approach
    • Verify drive motor nameplate parameters
    • Check supply voltage
    Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
    Trane · Tracer UC800 / Tracer CH530
    506 AFD Motor Current Overload (Ckt 2A)
    Lockout — Manual Reset

    AFD on compressor 2A reports motor current overload — same criteria as code 504 for circuit 2.

    Likely Causes
    • High differential pressure on circuit 2
    • Low voltage
    • Mechanical restriction on compressor 2A
    First Checks
    • Check circuit 2 condenser pressure
    • Verify drive parameters for ckt 2
    • Inspect compressor 2A for binding
    Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
    Trane · Tracer UC800 / Tracer CH530
    508 AFD Interrupt Failure (Ckt 1A)
    Lockout — Manual Reset

    AFD interrupt signal failure on compressor 1A — internal drive communication failure.

    Likely Causes
    • Drive control board failure
    • Noise on drive communication bus
    • Drive firmware issue
    First Checks
    • Power-cycle the drive after lockout
    • Check drive for internal fault codes
    • Inspect drive control wiring for noise sources
    Source: Trane Symbio 800 BACnet Points List BAS-PTS032A-EN (Dec 2024)
    Trane · Tracer UC800 / Tracer CH530
    D9 MP Reset Has Occurred
    Information

    Main processor successfully came out of reset and rebuilt application (power-up, software install, or reconfiguration). Informational — auto-clears.

    Likely Causes
    • Normal power-up
    • Software update applied
    • Watchdog-triggered reset
    First Checks
    • Review historic diagnostic list for prior faults that caused reset
    • Confirm no other active diagnostics
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    6B5 Unexpected Starter Shutdown
    Warning

    Starter module reported stopped when it should be running, and no starter diagnostic exists. Auto-logs and clears.

    Likely Causes
    • Power transient caused brief starter dropout
    • Starter communication glitch
    • Loose starter signal wiring
    First Checks
    • Review event history for frequency
    • Check starter signal wiring
    • Monitor supply voltage quality
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 for RTHD Chillers (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    CH530-LOCHW Low Chilled Water Temperature
    Shutdown

    Leaving chilled water temperature dropped below the Low Chilled Water Temperature Cutout setpoint (typically 36–40°F for water; lower for glycol). Non-latching auto-reset.

    Likely Causes
    • Low chilled water flow
    • Load turned off suddenly
    • Control setpoint set too close to low limit
    • Freeze protection activation
    First Checks
    • Verify chilled water pump is running and flow is established
    • Check LWCO setpoint vs. system requirements
    • Inspect for glycol concentration if applicable
    Source: Trane CVHE-SVU01E-EN, CenTraVac Operation & Maintenance Manual, Surplusgroup.com (2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-HICDP High Condenser Pressure
    Shutdown

    Condenser refrigerant pressure exceeded condenser pressure cutout setpoint (adaptive — typically 132 psiA for R-134a). Compressor unloads, then trips if not recovered.

    Likely Causes
    • Insufficient condenser water flow
    • High condenser water entering temperature
    • Non-condensables in refrigerant
    • Fouled condenser tubes
    First Checks
    • Verify condenser water flow and pump operation
    • Check cooling tower performance
    • Review condenser approach temperature
    • Check for non-condensables — purge unit if equipped
    Source: Trane CVHE-SVU01E-EN, CenTraVac Operation & Maintenance Manual, Surplusgroup.com (2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-SURGELMT Surge — Adaptive Control Limiting
    Warning

    Chiller surge detected; adaptive control is unloading compressor to prevent continued surge. Operating mode displayed as 'Surge'.

    Likely Causes
    • Low load condition forcing compressor to minimum capacity
    • High condenser / low evaporator pressure differential
    • IGV calibration out of spec
    • Hot gas bypass failure
    First Checks
    • Check system load — chiller may be oversized for current conditions
    • Verify IGV position and calibration
    • Confirm hot gas bypass (if installed) is operating
    • Review compressor differential pressure
    Source: Trane CVHE-SVU01E-EN, CenTraVac Operation & Maintenance Manual, Surplusgroup.com (2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-LKGV Loss of Evaporator Water Flow
    Shutdown

    Evaporator water flow not proven within 20 minutes of pump start command (4 min 15 s if pump override). Non-latching; clears when flow returns.

    Likely Causes
    • Evaporator pump failure
    • Closed isolation valve
    • Flow switch or differential pressure switch failed
    • Air pocket in chilled water loop
    First Checks
    • Verify pump is running (check amps)
    • Check flow switch or DP switch
    • Open all isolation valves
    • Bleed air from system
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    CH530-LKGVCD Loss of Condenser Water Flow
    Shutdown

    Condenser water flow not proven within the configured wait period. Non-latching; clears when flow returns.

    Likely Causes
    • Condenser pump failure
    • Closed condenser isolation valve
    • Cooling tower pump interlock not met
    • Flow switch malfunction
    First Checks
    • Verify condenser pump is running
    • Check all condenser isolation valves
    • Test condenser flow switch
    • Verify cooling tower pump interlock
    Source: Trane RLC-SVU006B-GB, Tracer TD7 with UC800 (Jul 2020)
    Trane · Tracer UC800 / Tracer CH530
    CH530-HIMOTR Motor Temperature Inhibit
    Shutdown

    Motor winding temperature exceeds the inhibit setpoint — chiller start blocked until temperature recovers.

    Likely Causes
    • Recent trip from overload
    • Failed motor temperature sensor
    • Inadequate motor cooling (refrigerant)
    First Checks
    • Allow adequate cooling time before restart
    • Check motor temperature sensor wiring and calibration
    • Verify motor refrigerant cooling circuit is open
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-HISUCPRS High Suction Pressure
    Shutdown

    Suction (evaporator) pressure exceeded the high suction pressure limit — compressor may be operating in a flooded condition.

    Likely Causes
    • EXV stuck open
    • High load condition
    • Refrigerant overcharge
    First Checks
    • Check EXV operation and control signal
    • Monitor entering chilled water temperature
    • Review refrigerant charge
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-RESTARTINH Restart Time Inhibit
    Information

    Anti-short-cycle timer preventing immediate restart after shutdown. Non-latching; auto-clears when timer expires.

    Likely Causes
    • Recent shutdown — normal protection
    • Chiller cycling on minor alarms
    First Checks
    • Allow timer to expire (typically 3–5 minutes)
    • Review cause of preceding shutdown
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-LOILPRS Low Oil Pressure During Pre-lubrication
    Lockout — Manual Reset

    Oil pressure not established during prelube period before compressor start.

    Likely Causes
    • Oil pump failure
    • Clogged oil strainer/filter
    • Low oil level in sump
    • Oil heater not maintaining temperature (viscous oil)
    First Checks
    • Verify oil pump operation
    • Check oil filter differential pressure
    • Verify oil level and temperature
    • Check oil heater energization during off-cycle
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-PHSIMBAL Phase Imbalance Limit
    Warning

    Phase current imbalance detected, causing capacity limit mode. Chiller continues to run but capacity is reduced.

    Likely Causes
    • Unbalanced utility supply
    • Partial single-phase condition
    • Motor winding degradation
    First Checks
    • Measure all three phase voltages
    • Check three-phase motor current balance
    • Notify utility if voltage imbalance
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-TRCRLOST Tracer Communication Lost
    Warning

    Communication to the Tracer building automation controller has been lost.

    Likely Causes
    • Network cable disconnected or damaged
    • Tracer controller offline or rebooting
    • Incorrect address or baud settings
    • LLID communication module failure
    First Checks
    • Check Tracer communication cable connections
    • Verify Tracer controller is online
    • Confirm LLID for Tracer comm shows green LED
    • Verify baud rate and address match
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-HIVACINH High Vacuum Inhibit
    Shutdown

    Oil sump pressure is below the high-vacuum inhibit threshold — chiller start blocked to protect compressor seals.

    Likely Causes
    • Non-condensables or refrigerant leak creating vacuum condition
    • Refrigerant undercharge
    • Chiller idle in cold ambient
    First Checks
    • Check system refrigerant pressure
    • Inspect for leaks
    • Warm chiller before starting in cold ambient
    • Check purge unit operation if applicable
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-LOILTMP Low Oil Temperature Inhibit
    Shutdown

    Oil temperature too low to permit safe start — typically <100°F. Oil heater must warm oil first.

    Likely Causes
    • Oil heater failure or not energized
    • Long idle period in cold ambient
    • High refrigerant concentration in oil
    First Checks
    • Verify oil heater is energized and functioning
    • Check oil temperature on display
    • Inspect oil heater wiring and element continuity
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-PURGERUN Purge Running — Excess Purge
    Warning

    Purge unit running excessively, indicating non-condensable buildup or refrigerant leak.

    Likely Causes
    • Air ingress through leaking valve packing
    • Refrigerant leak allowing air entry during vacuum
    • Purge unit malfunction
    First Checks
    • Perform leak check on entire refrigerant circuit
    • Check purge regeneration rate
    • Test purge unit operation
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-CURRLMT Current Limit — Running
    Information

    Compressor current has reached the active current limit setpoint — chiller is running but loading is inhibited.

    Likely Causes
    • Demand limit commanded from BAS or external signal
    • High differential pressure limiting capacity
    • Low supply voltage increasing current
    First Checks
    • Check active current limit setpoint source (BAS, external, panel)
    • Monitor condenser and evaporator conditions
    • Verify supply voltage
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    CH530-BASINHIB BAS/Tracer Inhibit
    Information

    Building automation system has commanded a run inhibit on the chiller.

    Likely Causes
    • Demand shed from BAS
    • Scheduled off command
    • Safety interlock from BAS-side logic
    First Checks
    • Check BAS schedule and setpoints
    • Verify no demand shed active
    • Review BAS logic for inhibit conditions
    Source: Trane CVHE-SVU01E-EN, CenTraVac O&M Manual (Surplusgroup.com 2005)
    Trane · Tracer UC800 / Tracer CH530
    AFDE-DRVFLT AFD Fault — Adaptive Frequency Drive
    Lockout — Manual Reset

    Adaptive Frequency Drive (variable speed centrifugal) has an active fault. Drive alarm message simultaneously displayed on AdaptiView.

    Likely Causes
    • Drive overcurrent or overtemperature
    • Drive cooling failure
    • Input power disturbance
    • Motor insulation fault
    First Checks
    • Read drive fault code on Tracer AdaptiView display
    • Inspect drive cooling fan and filter
    • Check DC bus voltage
    • Perform insulation resistance test on motor
    Source: Trane AFDE-SVU02E-EN, Liquid-Cooled Adaptive Frequency Drive with Tracer AdaptiView IOM (Jun 2020)
    Page 1 of 6