Back to HVAC/R Toolkit
    HVAC/R Toolkit

    Refrigeration Fault Codes

    Supermarket rack, walk-in, case controller, and ice machine codes for CPC/Emerson E2, Carel, Danfoss, Hussmann, Hill Phoenix, Manitowoc, Hoshizaki, Scotsman, Heatcraft, Copeland, and Bitzer.

    Refrigeration Fault Codes

    Supermarket rack, walk-in, case controller, and ice machine codes for CPC/Emerson E2, Carel, Danfoss, Hussmann, Hill Phoenix, Manitowoc, Hoshizaki, Scotsman, Heatcraft/Bohn, Copeland, and Bitzer.

    Coverage
    603codes
    15 controllers across 15 brands
    Filter by brand / controller
    Browsing all 603 codes · page 1 of 13
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CASE TEMP HI LIMIT EXCEEDED Case Temperature High Limit Exceeded
    Warning

    A single temperature sensor in a Standard Circuit or Case Control Circuit is reading above the defined case temperature high setpoint.

    Likely Causes
    • Failed evaporator fan motor
    • Blocked air flow
    • Defrost not terminating
    • Refrigerant leak on circuit
    • Faulty temp sensor
    First Checks
    • Verify fan operation in all evaporator sections
    • Check defrost termination sensor and setpoint
    • Pull gauge pressures on suction circuit
    • Inspect sensor resistance vs. temperature table
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CASE CLEANING WAS STARTED Case Cleaning Mode Initiated
    Information

    A case circuit has entered clean mode — fans and compressor are deactivated for cleaning cycle.

    Likely Causes
    • Manually triggered by operator
    • Scheduled cleaning event fired
    First Checks
    • Verify cleaning was intentional
    • Check that clean mode will time out correctly
    • Ensure case is returned to normal mode after cleaning
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALL NETWORK CONNECTIONS USED Echelon Network Connection Limit Reached
    Warning

    The Echelon controller has reached its maximum number of bound NVs (network variables).

    Likely Causes
    • Too many network devices added beyond controller capacity
    • Configuration error in I/O module addressing
    First Checks
    • Count active network bindings in E2 configuration
    • Remove duplicate or unused device bindings
    • Contact Emerson tech support for node expansion options
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALTERNATE HI LIMIT EXCEEDED Alternate High Limit Setpoint Exceeded
    Warning

    An analog value in an application using 'alternate' user setpoints has risen above its programmed Hi Limit setpoint.

    Likely Causes
    • Setpoint programmed too low relative to actual conditions
    • Sensor calibration drift
    • Refrigeration failure on circuit
    First Checks
    • Review alternate setpoint configuration
    • Calibrate or replace sensor
    • Check circuit refrigeration operation
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALTERNATE LOW LIMIT EXCEEDED Alternate Low Limit Setpoint Exceeded
    Warning

    An analog value in an application using 'alternate' user setpoints has fallen below its programmed Lo Limit setpoint.

    Likely Causes
    • Overcooling — liquid refrigerant flooding back
    • Setpoint too high
    • Sensor fault
    First Checks
    • Verify setpoint is appropriate
    • Check TXV/EEV superheat settings
    • Inspect sensor placement and resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    HEAT/COOL APPL NOT KEEPING SETPOINT AHU/Heat-Cool Application Not Achieving Setpoint
    Warning

    An Air Handling Unit or Heat/Cool application has not achieved setpoint for a prolonged period.

    Likely Causes
    • Insufficient refrigeration or heating capacity
    • Stuck reversing valve
    • Setpoint out of equipment range
    • Sensor failure
    First Checks
    • Check supply air temperature vs. setpoint
    • Verify reversing valve operation
    • Confirm equipment capacity vs. load
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION CELL IS LOST Application Cell Lost
    Shutdown

    An internal error has caused the loss of an entire application cell — priority 15 (high).

    Likely Causes
    • Controller memory corruption
    • Firmware update failure
    • Power loss during write operation
    First Checks
    • Reboot E2 controller
    • Reload application configuration from backup
    • If recurring, replace E2 controller
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION CONFIG HAS CHANGED Application Configuration Changed
    Information

    A user has changed the configuration of one of E2's applications — priority 99 (informational).

    Likely Causes
    • Authorized technician made parameter change
    • Unauthorized access
    First Checks
    • Review audit log for user identity
    • Verify new configuration is correct
    • Revert if unauthorized
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION SETPOINT HAS CHANGED Application Setpoint Changed
    Information

    A user has changed a setpoint in one of E2's applications — priority 99.

    Likely Causes
    • Technician setpoint adjustment
    • Automated demand response event
    First Checks
    • Confirm new setpoint is within design parameters
    • Log change in maintenance record
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ARTC/MULTIFLEX RTU OVERRIDE SWITCH STUCK ARTC/MultiFlex RTU Override Switch Stuck
    Warning

    An override switch on an ARTC/MultiFlex RTU has been ON for a prolonged period, suggesting possible switch failure — priority 20.

    Likely Causes
    • Failed override switch
    • Deliberate manual override left on
    • Wiring short on override input
    First Checks
    • Physically inspect override switch at ARTC/MultiFlex
    • Test switch continuity
    • Check wiring for shorts to ground
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ARTC/MULTIFLEX RTU RESET FROM POWER FAILURE ARTC/MultiFlex RTU Power Failure Reset
    Information

    An ARTC/MultiFlex RTU lost power and reset when power was restored — priority 50.

    Likely Causes
    • Power outage or momentary interruption
    • Loose wiring at RTU power terminals
    • Tripped breaker for RTU circuit
    First Checks
    • Verify 24VAC supply to RTU is stable
    • Check power wiring and connections
    • Review alarm log timestamps for correlation with utility events
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ATTEMPT TO WRITE PAST MEM. EOB Memory Write Beyond End of Buffer
    Warning

    The E2 attempted to write data to memory but the memory was full — priority 50.

    Likely Causes
    • Excessive logging or large alarm queue
    • Corrupted memory allocation
    • Firmware bug in older revision
    First Checks
    • Clear old logs and alarm history
    • Update E2 firmware to current release
    • If persistent, replace controller or reset to factory defaults
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    AVERAGE LOG STUCK-NO MEMORY Average Log Cannot Write — No Memory
    Warning

    Average log cannot be written because there is insufficient memory — priority 15.

    Likely Causes
    • Memory full from large data set
    • Flash memory failure
    • Too many data logging channels enabled
    First Checks
    • Delete oldest average log data
    • Reduce logging frequency or channel count
    • Check E2 memory health
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BAD MODEM Modem Not Functioning
    Warning

    The modem on this E2 is not functioning properly — priority 20.

    Likely Causes
    • Modem hardware failure
    • Incorrect modem initialization string
    • Phone line fault or disconnected
    First Checks
    • Test modem with a known-good phone line
    • Verify modem init string in E2 settings
    • Replace modem if hardware is confirmed bad
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BATTERY BACKED MEMORY LOST Battery Backed Memory Loss
    Warning

    Battery backed memory was lost not due to a cleanout operation — priority 30.

    Likely Causes
    • Dead or failed backup battery
    • Extended power outage exceeding battery life
    • Battery connection corrosion
    First Checks
    • Replace E2 backup battery (3V lithium)
    • Restore configuration from backup file
    • Verify clock and setpoints after restore
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BATT RUNTIME LIMIT Battery Runtime Limit Exceeded
    Information

    Battery runtime has exceeded 80% of the battery lifetime — priority 99.

    Likely Causes
    • Battery nearing end of service life
    • Excessive power outages draining battery
    First Checks
    • Schedule battery replacement at next PM visit
    • Check backup battery voltage
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BINDING INPUT TO OUTPUT FAILED Input-to-Output Binding Failed
    Warning

    A valid connection could not be made between an input and an output during network binding — priority 20.

    Likely Causes
    • I/O module offline or not communicating
    • Incorrect node address on I/O module
    • Echelon network wiring fault
    First Checks
    • Verify I/O module LEDs are active
    • Check Echelon network wiring polarity
    • Re-scan network and re-bind offline modules
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BIOS/BIOS EXT. UPDATE FAILED BIOS/BIOS Extension Update Failed
    Warning

    An update to the E2's BIOS has failed — priority 20.

    Likely Causes
    • Interrupted update process (power loss)
    • Corrupted update file
    • Incompatible firmware version
    First Checks
    • Re-attempt update with verified firmware file
    • Ensure stable power during update
    • Contact Emerson support if controller is bricked
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CAN'T SET HARDWARE CLOCK Hardware Clock Cannot Be Set
    Warning

    The E2 is unable to change the time on its hardware clock.

    Likely Causes
    • Hardware clock chip failure
    • Backup battery dead preventing clock maintenance
    • Firmware issue
    First Checks
    • Replace backup battery
    • Attempt time sync via E2 time settings menu
    • Replace controller if clock chip is faulty
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DEFROST DID NOT COMPLETE Defrost Did Not Complete
    Warning

    A defrost cycle did not terminate on temperature — terminated on backup time limit instead.

    Likely Causes
    • Faulty defrost termination thermostat or sensor
    • Heater element failure
    • Ice buildup too heavy to clear in allotted time
    • Refrigerant overcharge causing excessive frost
    First Checks
    • Check defrost termination sensor resistance
    • Verify heater element continuity
    • Increase max defrost time if loads warrant
    • Pull refrigerant charge if overcalculated
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DEFROST WAS SKIPPED Scheduled Defrost Was Skipped
    Information

    A scheduled defrost was skipped, typically due to the circuit being in another state.

    Likely Causes
    • Circuit in override mode
    • Defrost already in progress from another initiation
    • Case door alarm suppressing defrost
    First Checks
    • Check E2 defrost schedule configuration
    • Verify no manual override is active
    • Review defrost log for frequency
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2 POWER FAILED E2 Controller Power Failure
    Warning

    The E2 controller lost power and has restarted. Logged on power-up to track outage events.

    Likely Causes
    • AC power outage
    • UPS failure
    • Tripped breaker on controller panel
    First Checks
    • Check utility power history and UPS logs
    • Inspect breaker and supply wiring
    • Verify all I/O modules came back online
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ECHELON COMM FAILURE Echelon Network Communication Failure
    Warning

    Communication on the Echelon LON network has failed or a node has gone offline.

    Likely Causes
    • Broken or shorted Echelon network cable
    • Failed I/O module
    • Terminator missing from network ends
    • Node address conflict
    First Checks
    • Inspect Echelon wiring for breaks or shorts
    • Verify correct termination at both cable ends
    • Check I/O module status LEDs
    • Re-scan network from E2
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SUCTION PRESSURE HI LIMIT Suction Pressure High Limit Alarm
    Warning

    Suction pressure has risen above the programmed high setpoint, indicating insufficient compression or excessive load.

    Likely Causes
    • Compressor failure or underloaded rack
    • Excessive load on suction group
    • Liquid slugging back to compressor
    • Pressure transducer calibration drift
    First Checks
    • Verify suction pressure with gauge manifold
    • Check rack compressor staging and lead/lag sequence
    • Inspect suction line for liquid flooding
    • Calibrate or replace suction transducer
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SUCTION PRESSURE LO LIMIT Suction Pressure Low Limit Alarm
    Warning

    Suction pressure has dropped below the programmed low setpoint, risking compressor damage from floodback or low pressure cutout.

    Likely Causes
    • Undercharged system or refrigerant leak
    • TXV/EEV starving evaporator
    • Restricted liquid line filter-drier
    • Low ambient causing head pressure to drop
    First Checks
    • Pull manifold gauges to confirm pressure
    • Check subcooling and superheat readings
    • Inspect filter-drier for pressure drop
    • Check system charge
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DISCHARGE PRESSURE HI LIMIT Discharge Pressure High Limit Alarm
    Warning

    Discharge pressure has exceeded the programmed high setpoint — risk of high pressure cutout on compressors.

    Likely Causes
    • Dirty or fouled condenser coil
    • Condenser fan failure
    • Refrigerant overcharge
    • High ambient temperature
    • Non-condensables in system
    First Checks
    • Check condenser fan operation
    • Clean condenser coils
    • Verify head pressure control operation
    • Pull discharge manifold pressure
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMPRESSOR CIRCUIT BREAKER TRIP Compressor Circuit Breaker Tripped
    Shutdown

    A compressor's circuit breaker has tripped. Unit protection event.

    Likely Causes
    • Compressor locked rotor or overload
    • Contactor weld causing run-on
    • Wiring short
    • Overloaded circuit
    First Checks
    • Do not immediately reset — check compressor amp draw
    • Inspect contactor for welded contacts
    • Check wiring at compressor terminals
    • Verify motor winding resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMPRESSOR OVERLOAD TRIP Compressor Thermal Overload Trip
    Shutdown

    Compressor internal overload protector or external OLP has opened, shutting down the compressor.

    Likely Causes
    • High discharge temperature
    • Single-phasing or phase imbalance
    • Liquid slugging on startup
    • Failed compressor motor windings
    First Checks
    • Allow 20–30 min cool-down before reset
    • Check three-phase voltage and current balance
    • Verify crankcase heater is energized during off cycles
    • Measure motor winding resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMP OIL PRESSURE FAIL Compressor Oil Pressure Failure
    Lockout — Manual Reset

    Oil differential pressure switch did not close within the startup time window, or opened during operation.

    Likely Causes
    • Low oil level in crankcase
    • Failed oil pump
    • Clogged oil filter screen
    • Oil foaming on startup
    • Defective oil pressure switch
    First Checks
    • Check oil sight glass level
    • Verify oil pressure switch setpoint and wiring
    • Inspect for oil foam by sight glass
    • Replace oil filter if restricted
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    HIGH PRESSURE CUTOUT High Pressure Safety Cutout Opened
    Lockout — Manual Reset

    The high pressure safety switch (HPCO) has opened, shutting down the compressor. Requires manual reset.

    Likely Causes
    • Blocked condenser airflow
    • Refrigerant overcharge
    • Non-condensables in system
    • Failed condenser fan
    • Discharge service valve partially closed
    First Checks
    • Check discharge pressure with manifold gauge before resetting
    • Inspect condenser fan operation
    • Look for airflow obstructions at condenser
    • Verify discharge service valve is fully open
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    LOW PRESSURE CUTOUT Low Pressure Safety Cutout Opened
    Shutdown

    The low pressure safety switch has opened. May auto-reset if LPCO is set for automatic reset.

    Likely Causes
    • Refrigerant leak reducing system charge
    • TXV starving or ice on evaporator
    • Liquid line solenoid not opening
    • Blocked suction strainer
    First Checks
    • Check suction pressure with manifold gauge
    • Verify LLSV is opening on call for cooling
    • Inspect suction strainer for blockage
    • Check for leaks with electronic detector
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SENSOR FAILURE — PROBE OPEN/SHORT Temperature Sensor Open or Short Circuit
    Warning

    A temperature probe input is reading an open circuit (>300k ohm) or short circuit (<10 ohm), indicating sensor or wiring failure.

    Likely Causes
    • Broken sensor wire
    • Moisture ingress in sensor connector
    • Sensor pulled from mounting bracket
    • Failed sensor NTC element
    First Checks
    • Check sensor resistance at controller terminal — compare to temp/resistance chart
    • Inspect wiring for cuts or crimps
    • Verify sensor connector is seated
    • Replace sensor if resistance is out of range
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DOOR ALARM Case Door Open Alarm
    Warning

    A case door has been open longer than the programmed door alarm delay setpoint.

    Likely Causes
    • Door left open by staff
    • Door switch failure
    • Damaged door gasket preventing full closure
    • Broken door hinge
    First Checks
    • Physically verify door is closed
    • Test door magnetic switch continuity
    • Inspect door gaskets for compression seal
    • Review E2 door alarm delay setpoint
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    NETWORK DEVICE OFFLINE Network I/O Device Offline
    Warning

    An I/O board or device on the E2 network has gone offline or stopped communicating.

    Likely Causes
    • Power loss to I/O module
    • Echelon wiring fault or break
    • Corrupted node firmware
    • Duplicate node address
    First Checks
    • Check 24VAC supply to offline module
    • Inspect LON wiring at affected node
    • Reload node firmware from E2 if accessible
    • Swap module to test
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALL-NETW-USED All Network Connections Used
    Warning

    Echelon controller reached its limit of bound NVs

    Likely Causes
    • Too many devices on Echelon network
    • Network variable table full
    • Configuration error
    First Checks
    • Review NV count in E2 network config
    • Remove unused bindings
    • Check Echelon network commissioning
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALT-HI-LIM Alternate Hi Limit Exceeded
    Warning

    Analog value using alternate setpoints rose above Hi Limit

    Likely Causes
    • Refrigeration circuit temperature out of range
    • Incorrect alternate setpoint
    • Sensor drift
    First Checks
    • Check alternate Hi Limit setpoint
    • Verify sensor calibration
    • Inspect associated circuit
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALT-LO-LIM Alternate Low Limit Exceeded
    Warning

    Analog value using alternate setpoints fell below Lo Limit

    Likely Causes
    • Temperature dropping below configured low limit
    • Setpoint configured incorrectly
    • Sensor failure
    First Checks
    • Check alternate Lo Limit setpoint
    • Verify sensor reading accuracy
    • Inspect refrigeration components
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-APPL-CELL-LOST Application Cell Is Lost
    Shutdown

    Internal error caused loss of an entire application cell

    Likely Causes
    • Memory corruption
    • Power interruption during configuration write
    • Firmware defect
    First Checks
    • Perform E2 cold reset
    • Restore from backup configuration
    • Contact Emerson support if recurring
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-APPL-CFG-CHG Application Config Has Changed
    Information

    A user changed the configuration of one of E2 applications

    Likely Causes
    • Unauthorized user changed application config
    • Normal commissioning activity
    • Remote configuration session
    First Checks
    • Verify configuration change was intended
    • Review audit log for user ID
    • Confirm setpoints are correct
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ARTC-OVERRIDE ARTC/MultiFlex RTU Override Switch Stuck
    Warning

    Override switch ON for prolonged period

    Likely Causes
    • Switch physically stuck in ON position
    • Wiring short holding switch closed
    • Component failure
    First Checks
    • Physically inspect override switch
    • Measure switch contact resistance
    • Replace switch if stuck
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ARTC-RESET ARTC/MultiFlex RTU Reset From Power Failure
    Information

    RTU lost power and reset when power restored

    Likely Causes
    • Power interruption at RTU
    • Loose wiring at power terminal
    • Branch circuit breaker tripped
    First Checks
    • Check power connections at RTU
    • Verify branch circuit breaker status
    • Review power quality
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BAT-MEM-LOST Battery Backed Memory Lost
    Warning

    Battery backed memory loss not due to cleanout

    Likely Causes
    • Battery depleted or failed
    • Battery connection issue
    • PCB damage
    First Checks
    • Replace RTC battery
    • Check battery connector on main board
    • Review memory retention after battery change
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BATT-RUNTIME Battery Runtime Limit
    Warning

    Battery runtime has exceeded 80% of battery lifetime

    Likely Causes
    • Battery aging past replacement threshold
    • High battery drain
    • Poor battery contact
    First Checks
    • Replace battery immediately
    • Check battery voltage
    • Verify no excessive drain circuit
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BIND-FAIL Binding Input To Output Failed
    Warning

    Valid connection could not be made between input and output

    Likely Causes
    • Echelon network error
    • Device offline when binding attempted
    • Software configuration mismatch
    First Checks
    • Check device status on network
    • Re-attempt binding
    • Verify device type matches configuration
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BIOS-UPDATE-FAIL BIOS/BIOS Ext. Update Failed
    Warning

    Update to E2 BIOS has failed

    Likely Causes
    • Corrupted firmware file
    • Power interruption during update
    • Incompatible firmware version
    First Checks
    • Retry firmware update
    • Verify firmware file integrity
    • Ensure power stable during update
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CANT-SET-HW-CLK Can't Set Hardware Clock
    Warning

    E2 unable to change time on hardware clock

    Likely Causes
    • RTC chip failure
    • Battery depleted causing clock reset loop
    • Firmware issue
    First Checks
    • Check RTC battery voltage
    • Replace RTC battery
    • If persists replace main board
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CASE-CTRL-HI Case Temp Hi Limit Exceeded
    Warning

    Case temp sensor recording above defined case high setpoint

    Likely Causes
    • Refrigeration system not cooling adequately
    • Defrost cycle running too long
    • Door gasket failure
    • Sensor failure reading high
    First Checks
    • Check case temperature setpoint
    • Verify cooling is active
    • Inspect door seals
    • Check defrost termination
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CASE-CTRL-LO Case Temp Low Limit Exceeded
    Information

    Case temp sensor recording below defined case temperature low setpoint

    Likely Causes
    • Setpoint too cold
    • Defrost terminated prematurely
    • Sensor failure reading low
    First Checks
    • Review low temperature setpoint
    • Check defrost schedule
    • Verify sensor accuracy
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CHECKIT-FAILED Checkit Sensor Has Failed
    Warning

    Checkit sensor returning an invalid temperature value

    Likely Causes
    • Sensor probe open circuit
    • Wiring break
    • Connector corrosion
    • Probe physically damaged
    First Checks
    • Measure sensor resistance
    • Inspect wiring from sensor to board
    • Replace Checkit sensor probe
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CHECKIT-ALARM Checkit Sensor Is Alarming
    Warning

    Checkit sensor on Suction Group recording high temperature

    Likely Causes
    • Refrigerant loss on that circuit
    • EEV stuck closed
    • High ambient reducing capacity
    First Checks
    • Inspect refrigeration on associated circuit
    • Check EEV operation
    • Pull refrigerant charge
    Source: scribd.com
    Page 1 of 13