Back to HVAC/R Toolkit

    Refrigeration Fault Codes

    Supermarket rack, walk-in, case controller, and ice machine codes for CPC/Emerson E2, Carel, Danfoss, Hussmann, Hill Phoenix, Manitowoc, Hoshizaki, Scotsman, Heatcraft, Copeland, and Bitzer.

    Built by Top Industrial Talent for the HVAC/R technicians who rely on accurate field data every day.

    Refrigeration Fault Codes

    Supermarket rack, walk-in, case controller, and ice machine codes for CPC/Emerson E2, Carel, Danfoss, Hussmann, Hill Phoenix, Manitowoc, Hoshizaki, Scotsman, Heatcraft/Bohn, Copeland, and Bitzer.

    Coverage
    603codes
    15 controllers across 15 brands
    Filter by brand / controller
    Browsing all 603 codes · page 1 of 13
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CASE TEMP HI LIMIT EXCEEDED , Case Temperature High Limit Exceeded
    Warning

    A single temperature sensor in a Standard Circuit or Case Control Circuit is reading above the defined case temperature high setpoint.

    Likely Causes
    • Failed evaporator fan motor
    • Blocked air flow
    • Defrost not terminating
    • Refrigerant leak on circuit
    • Faulty temp sensor
    First Checks
    • Verify fan operation in all evaporator sections
    • Check defrost termination sensor and setpoint
    • Pull gauge pressures on suction circuit
    • Inspect sensor resistance vs. temperature table
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CASE CLEANING WAS STARTED , Case Cleaning Mode Initiated
    Information

    A case circuit has entered clean mode, fans and compressor are deactivated for cleaning cycle.

    Likely Causes
    • Manually triggered by operator
    • Scheduled cleaning event fired
    First Checks
    • Verify cleaning was intentional
    • Check that clean mode will time out correctly
    • Ensure case is returned to normal mode after cleaning
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALL NETWORK CONNECTIONS USED , Echelon Network Connection Limit Reached
    Warning

    The Echelon controller has reached its maximum number of bound NVs (network variables).

    Likely Causes
    • Too many network devices added beyond controller capacity
    • Configuration error in I/O module addressing
    First Checks
    • Count active network bindings in E2 configuration
    • Remove duplicate or unused device bindings
    • Contact Emerson tech support for node expansion options
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALTERNATE HI LIMIT EXCEEDED , Alternate High Limit Setpoint Exceeded
    Warning

    An analog value in an application using 'alternate' user setpoints has risen above its programmed Hi Limit setpoint.

    Likely Causes
    • Setpoint programmed too low relative to actual conditions
    • Sensor calibration drift
    • Refrigeration failure on circuit
    First Checks
    • Review alternate setpoint configuration
    • Calibrate or replace sensor
    • Check circuit refrigeration operation
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ALTERNATE LOW LIMIT EXCEEDED , Alternate Low Limit Setpoint Exceeded
    Warning

    An analog value in an application using 'alternate' user setpoints has fallen below its programmed Lo Limit setpoint.

    Likely Causes
    • Overcooling, liquid refrigerant flooding back
    • Setpoint too high
    • Sensor fault
    First Checks
    • Verify setpoint is appropriate
    • Check TXV/EEV superheat settings
    • Inspect sensor placement and resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    HEAT/COOL APPL NOT KEEPING SETPOINT , AHU/Heat-Cool Application Not Achieving Setpoint
    Warning

    An Air Handling Unit or Heat/Cool application has not achieved setpoint for a prolonged period.

    Likely Causes
    • Insufficient refrigeration or heating capacity
    • Stuck reversing valve
    • Setpoint out of equipment range
    • Sensor failure
    First Checks
    • Check supply air temperature vs. setpoint
    • Verify reversing valve operation
    • Confirm equipment capacity vs. load
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION CELL IS LOST , Application Cell Lost
    Shutdown

    An internal error has caused the loss of an entire application cell, priority 15 (high).

    Likely Causes
    • Controller memory corruption
    • Firmware update failure
    • Power loss during write operation
    First Checks
    • Reboot E2 controller
    • Reload application configuration from backup
    • If recurring, replace E2 controller
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION CONFIG HAS CHANGED , Application Configuration Changed
    Information

    A user has changed the configuration of one of E2's applications, priority 99 (informational).

    Likely Causes
    • Authorized technician made parameter change
    • Unauthorized access
    First Checks
    • Review audit log for user identity
    • Verify new configuration is correct
    • Revert if unauthorized
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    APPLICATION SETPOINT HAS CHANGED , Application Setpoint Changed
    Information

    A user has changed a setpoint in one of E2's applications, priority 99.

    Likely Causes
    • Technician setpoint adjustment
    • Automated demand response event
    First Checks
    • Confirm new setpoint is within design parameters
    • Log change in maintenance record
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ARTC/MULTIFLEX RTU OVERRIDE SWITCH STUCK , ARTC/MultiFlex RTU Override Switch Stuck
    Warning

    An override switch on an ARTC/MultiFlex RTU has been ON for a prolonged period, suggesting possible switch failure, priority 20.

    Likely Causes
    • Failed override switch
    • Deliberate manual override left on
    • Wiring short on override input
    First Checks
    • Physically inspect override switch at ARTC/MultiFlex
    • Test switch continuity
    • Check wiring for shorts to ground
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ARTC/MULTIFLEX RTU RESET FROM POWER FAILURE , ARTC/MultiFlex RTU Power Failure Reset
    Information

    An ARTC/MultiFlex RTU lost power and reset when power was restored, priority 50.

    Likely Causes
    • Power outage or momentary interruption
    • Loose wiring at RTU power terminals
    • Tripped breaker for RTU circuit
    First Checks
    • Verify 24VAC supply to RTU is stable
    • Check power wiring and connections
    • Review alarm log timestamps for correlation with utility events
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ATTEMPT TO WRITE PAST MEM. EOB , Memory Write Beyond End of Buffer
    Warning

    The E2 attempted to write data to memory but the memory was full, priority 50.

    Likely Causes
    • Excessive logging or large alarm queue
    • Corrupted memory allocation
    • Firmware bug in older revision
    First Checks
    • Clear old logs and alarm history
    • Update E2 firmware to current release
    • If persistent, replace controller or reset to factory defaults
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    AVERAGE LOG STUCK-NO MEMORY , Average Log Cannot Write, No Memory
    Warning

    Average log cannot be written because there is insufficient memory, priority 15.

    Likely Causes
    • Memory full from large data set
    • Flash memory failure
    • Too many data logging channels enabled
    First Checks
    • Delete oldest average log data
    • Reduce logging frequency or channel count
    • Check E2 memory health
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BAD MODEM , Modem Not Functioning
    Warning

    The modem on this E2 is not functioning properly, priority 20.

    Likely Causes
    • Modem hardware failure
    • Incorrect modem initialization string
    • Phone line fault or disconnected
    First Checks
    • Test modem with a known-good phone line
    • Verify modem init string in E2 settings
    • Replace modem if hardware is confirmed bad
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BATTERY BACKED MEMORY LOST , Battery Backed Memory Loss
    Warning

    Battery backed memory was lost not due to a cleanout operation, priority 30.

    Likely Causes
    • Dead or failed backup battery
    • Extended power outage exceeding battery life
    • Battery connection corrosion
    First Checks
    • Replace E2 backup battery (3V lithium)
    • Restore configuration from backup file
    • Verify clock and setpoints after restore
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BATT RUNTIME LIMIT , Battery Runtime Limit Exceeded
    Information

    Battery runtime has exceeded 80% of the battery lifetime, priority 99.

    Likely Causes
    • Battery nearing end of service life
    • Excessive power outages draining battery
    First Checks
    • Schedule battery replacement at next PM visit
    • Check backup battery voltage
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BINDING INPUT TO OUTPUT FAILED , Input-to-Output Binding Failed
    Warning

    A valid connection could not be made between an input and an output during network binding, priority 20.

    Likely Causes
    • I/O module offline or not communicating
    • Incorrect node address on I/O module
    • Echelon network wiring fault
    First Checks
    • Verify I/O module LEDs are active
    • Check Echelon network wiring polarity
    • Re-scan network and re-bind offline modules
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    BIOS/BIOS EXT. UPDATE FAILED , BIOS/BIOS Extension Update Failed
    Warning

    An update to the E2's BIOS has failed, priority 20.

    Likely Causes
    • Interrupted update process (power loss)
    • Corrupted update file
    • Incompatible firmware version
    First Checks
    • Re-attempt update with verified firmware file
    • Ensure stable power during update
    • Contact Emerson support if controller is bricked
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    CAN'T SET HARDWARE CLOCK , Hardware Clock Cannot Be Set
    Warning

    The E2 is unable to change the time on its hardware clock.

    Likely Causes
    • Hardware clock chip failure
    • Backup battery dead preventing clock maintenance
    • Firmware issue
    First Checks
    • Replace backup battery
    • Attempt time sync via E2 time settings menu
    • Replace controller if clock chip is faulty
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DEFROST DID NOT COMPLETE , Defrost Did Not Complete
    Warning

    A defrost cycle did not terminate on temperature, terminated on backup time limit instead.

    Likely Causes
    • Faulty defrost termination thermostat or sensor
    • Heater element failure
    • Ice buildup too heavy to clear in allotted time
    • Refrigerant overcharge causing excessive frost
    First Checks
    • Check defrost termination sensor resistance
    • Verify heater element continuity
    • Increase max defrost time if loads warrant
    • Pull refrigerant charge if overcalculated
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DEFROST WAS SKIPPED , Scheduled Defrost Was Skipped
    Information

    A scheduled defrost was skipped, typically due to the circuit being in another state.

    Likely Causes
    • Circuit in override mode
    • Defrost already in progress from another initiation
    • Case door alarm suppressing defrost
    First Checks
    • Check E2 defrost schedule configuration
    • Verify no manual override is active
    • Review defrost log for frequency
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2 POWER FAILED , E2 Controller Power Failure
    Warning

    The E2 controller lost power and has restarted. Logged on power-up to track outage events.

    Likely Causes
    • AC power outage
    • UPS failure
    • Tripped breaker on controller panel
    First Checks
    • Check utility power history and UPS logs
    • Inspect breaker and supply wiring
    • Verify all I/O modules came back online
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    ECHELON COMM FAILURE , Echelon Network Communication Failure
    Warning

    Communication on the Echelon LON network has failed or a node has gone offline.

    Likely Causes
    • Broken or shorted Echelon network cable
    • Failed I/O module
    • Terminator missing from network ends
    • Node address conflict
    First Checks
    • Inspect Echelon wiring for breaks or shorts
    • Verify correct termination at both cable ends
    • Check I/O module status LEDs
    • Re-scan network from E2
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SUCTION PRESSURE HI LIMIT , Suction Pressure High Limit Alarm
    Warning

    Suction pressure has risen above the programmed high setpoint, indicating insufficient compression or excessive load.

    Likely Causes
    • Compressor failure or underloaded rack
    • Excessive load on suction group
    • Liquid slugging back to compressor
    • Pressure transducer calibration drift
    First Checks
    • Verify suction pressure with gauge manifold
    • Check rack compressor staging and lead/lag sequence
    • Inspect suction line for liquid flooding
    • Calibrate or replace suction transducer
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SUCTION PRESSURE LO LIMIT , Suction Pressure Low Limit Alarm
    Warning

    Suction pressure has dropped below the programmed low setpoint, risking compressor damage from floodback or low pressure cutout.

    Likely Causes
    • Undercharged system or refrigerant leak
    • TXV/EEV starving evaporator
    • Restricted liquid line filter-drier
    • Low ambient causing head pressure to drop
    First Checks
    • Pull manifold gauges to confirm pressure
    • Check subcooling and superheat readings
    • Inspect filter-drier for pressure drop
    • Check system charge
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DISCHARGE PRESSURE HI LIMIT , Discharge Pressure High Limit Alarm
    Warning

    Discharge pressure has exceeded the programmed high setpoint, risk of high pressure cutout on compressors.

    Likely Causes
    • Dirty or fouled condenser coil
    • Condenser fan failure
    • Refrigerant overcharge
    • High ambient temperature
    • Non-condensables in system
    First Checks
    • Check condenser fan operation
    • Clean condenser coils
    • Verify head pressure control operation
    • Pull discharge manifold pressure
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMPRESSOR CIRCUIT BREAKER TRIP , Compressor Circuit Breaker Tripped
    Shutdown

    A compressor's circuit breaker has tripped. Unit protection event.

    Likely Causes
    • Compressor locked rotor or overload
    • Contactor weld causing run-on
    • Wiring short
    • Overloaded circuit
    First Checks
    • Do not immediately reset, check compressor amp draw
    • Inspect contactor for welded contacts
    • Check wiring at compressor terminals
    • Verify motor winding resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMPRESSOR OVERLOAD TRIP , Compressor Thermal Overload Trip
    Shutdown

    Compressor internal overload protector or external OLP has opened, shutting down the compressor.

    Likely Causes
    • High discharge temperature
    • Single-phasing or phase imbalance
    • Liquid slugging on startup
    • Failed compressor motor windings
    First Checks
    • Allow 20–30 min cool-down before reset
    • Check three-phase voltage and current balance
    • Verify crankcase heater is energized during off cycles
    • Measure motor winding resistance
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    COMP OIL PRESSURE FAIL , Compressor Oil Pressure Failure
    Lockout, Manual Reset

    Oil differential pressure switch did not close within the startup time window, or opened during operation.

    Likely Causes
    • Low oil level in crankcase
    • Failed oil pump
    • Clogged oil filter screen
    • Oil foaming on startup
    • Defective oil pressure switch
    First Checks
    • Check oil sight glass level
    • Verify oil pressure switch setpoint and wiring
    • Inspect for oil foam by sight glass
    • Replace oil filter if restricted
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    HIGH PRESSURE CUTOUT , High Pressure Safety Cutout Opened
    Lockout, Manual Reset

    The high pressure safety switch (HPCO) has opened, shutting down the compressor. Requires manual reset.

    Likely Causes
    • Blocked condenser airflow
    • Refrigerant overcharge
    • Non-condensables in system
    • Failed condenser fan
    • Discharge service valve partially closed
    First Checks
    • Check discharge pressure with manifold gauge before resetting
    • Inspect condenser fan operation
    • Look for airflow obstructions at condenser
    • Verify discharge service valve is fully open
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    LOW PRESSURE CUTOUT , Low Pressure Safety Cutout Opened
    Shutdown

    The low pressure safety switch has opened. May auto-reset if LPCO is set for automatic reset.

    Likely Causes
    • Refrigerant leak reducing system charge
    • TXV starving or ice on evaporator
    • Liquid line solenoid not opening
    • Blocked suction strainer
    First Checks
    • Check suction pressure with manifold gauge
    • Verify LLSV is opening on call for cooling
    • Inspect suction strainer for blockage
    • Check for leaks with electronic detector
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    SENSOR FAILURE, PROBE OPEN/SHORT , Temperature Sensor Open or Short Circuit
    Warning

    A temperature probe input is reading an open circuit (>300k ohm) or short circuit (<10 ohm), indicating sensor or wiring failure.

    Likely Causes
    • Broken sensor wire
    • Moisture ingress in sensor connector
    • Sensor pulled from mounting bracket
    • Failed sensor NTC element
    First Checks
    • Check sensor resistance at controller terminal, compare to temp/resistance chart
    • Inspect wiring for cuts or crimps
    • Verify sensor connector is seated
    • Replace sensor if resistance is out of range
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    DOOR ALARM , Case Door Open Alarm
    Warning

    A case door has been open longer than the programmed door alarm delay setpoint.

    Likely Causes
    • Door left open by staff
    • Door switch failure
    • Damaged door gasket preventing full closure
    • Broken door hinge
    First Checks
    • Physically verify door is closed
    • Test door magnetic switch continuity
    • Inspect door gaskets for compression seal
    • Review E2 door alarm delay setpoint
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    NETWORK DEVICE OFFLINE , Network I/O Device Offline
    Warning

    An I/O board or device on the E2 network has gone offline or stopped communicating.

    Likely Causes
    • Power loss to I/O module
    • Echelon wiring fault or break
    • Corrupted node firmware
    • Duplicate node address
    First Checks
    • Check 24VAC supply to offline module
    • Inspect LON wiring at affected node
    • Reload node firmware from E2 if accessible
    • Swap module to test
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALL-NETW-USED , All Network Connections Used
    Warning

    Echelon controller reached its limit of bound NVs

    Likely Causes
    • Too many devices on Echelon network
    • Network variable table full
    • Configuration error
    First Checks
    • Review NV count in E2 network config
    • Remove unused bindings
    • Check Echelon network commissioning
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALT-HI-LIM , Alternate Hi Limit Exceeded
    Warning

    Analog value using alternate setpoints rose above Hi Limit

    Likely Causes
    • Refrigeration circuit temperature out of range
    • Incorrect alternate setpoint
    • Sensor drift
    First Checks
    • Check alternate Hi Limit setpoint
    • Verify sensor calibration
    • Inspect associated circuit
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ALT-LO-LIM , Alternate Low Limit Exceeded
    Warning

    Analog value using alternate setpoints fell below Lo Limit

    Likely Causes
    • Temperature dropping below configured low limit
    • Setpoint configured incorrectly
    • Sensor failure
    First Checks
    • Check alternate Lo Limit setpoint
    • Verify sensor reading accuracy
    • Inspect refrigeration components
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-APPL-CELL-LOST , Application Cell Is Lost
    Shutdown

    Internal error caused loss of an entire application cell

    Likely Causes
    • Memory corruption
    • Power interruption during configuration write
    • Firmware defect
    First Checks
    • Perform E2 cold reset
    • Restore from backup configuration
    • Contact Emerson support if recurring
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-APPL-CFG-CHG , Application Config Has Changed
    Information

    A user changed the configuration of one of E2 applications

    Likely Causes
    • Unauthorized user changed application config
    • Normal commissioning activity
    • Remote configuration session
    First Checks
    • Verify configuration change was intended
    • Review audit log for user ID
    • Confirm setpoints are correct
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ARTC-OVERRIDE , ARTC/MultiFlex RTU Override Switch Stuck
    Warning

    Override switch ON for prolonged period

    Likely Causes
    • Switch physically stuck in ON position
    • Wiring short holding switch closed
    • Component failure
    First Checks
    • Physically inspect override switch
    • Measure switch contact resistance
    • Replace switch if stuck
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-ARTC-RESET , ARTC/MultiFlex RTU Reset From Power Failure
    Information

    RTU lost power and reset when power restored

    Likely Causes
    • Power interruption at RTU
    • Loose wiring at power terminal
    • Branch circuit breaker tripped
    First Checks
    • Check power connections at RTU
    • Verify branch circuit breaker status
    • Review power quality
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BAT-MEM-LOST , Battery Backed Memory Lost
    Warning

    Battery backed memory loss not due to cleanout

    Likely Causes
    • Battery depleted or failed
    • Battery connection issue
    • PCB damage
    First Checks
    • Replace RTC battery
    • Check battery connector on main board
    • Review memory retention after battery change
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BATT-RUNTIME , Battery Runtime Limit
    Warning

    Battery runtime has exceeded 80% of battery lifetime

    Likely Causes
    • Battery aging past replacement threshold
    • High battery drain
    • Poor battery contact
    First Checks
    • Replace battery immediately
    • Check battery voltage
    • Verify no excessive drain circuit
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BIND-FAIL , Binding Input To Output Failed
    Warning

    Valid connection could not be made between input and output

    Likely Causes
    • Echelon network error
    • Device offline when binding attempted
    • Software configuration mismatch
    First Checks
    • Check device status on network
    • Re-attempt binding
    • Verify device type matches configuration
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-BIOS-UPDATE-FAIL , BIOS/BIOS Ext. Update Failed
    Warning

    Update to E2 BIOS has failed

    Likely Causes
    • Corrupted firmware file
    • Power interruption during update
    • Incompatible firmware version
    First Checks
    • Retry firmware update
    • Verify firmware file integrity
    • Ensure power stable during update
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CANT-SET-HW-CLK , Can't Set Hardware Clock
    Warning

    E2 unable to change time on hardware clock

    Likely Causes
    • RTC chip failure
    • Battery depleted causing clock reset loop
    • Firmware issue
    First Checks
    • Check RTC battery voltage
    • Replace RTC battery
    • If persists replace main board
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CASE-CTRL-HI , Case Temp Hi Limit Exceeded
    Warning

    Case temp sensor recording above defined case high setpoint

    Likely Causes
    • Refrigeration system not cooling adequately
    • Defrost cycle running too long
    • Door gasket failure
    • Sensor failure reading high
    First Checks
    • Check case temperature setpoint
    • Verify cooling is active
    • Inspect door seals
    • Check defrost termination
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CASE-CTRL-LO , Case Temp Low Limit Exceeded
    Information

    Case temp sensor recording below defined case temperature low setpoint

    Likely Causes
    • Setpoint too cold
    • Defrost terminated prematurely
    • Sensor failure reading low
    First Checks
    • Review low temperature setpoint
    • Check defrost schedule
    • Verify sensor accuracy
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CHECKIT-FAILED , Checkit Sensor Has Failed
    Warning

    Checkit sensor returning an invalid temperature value

    Likely Causes
    • Sensor probe open circuit
    • Wiring break
    • Connector corrosion
    • Probe physically damaged
    First Checks
    • Measure sensor resistance
    • Inspect wiring from sensor to board
    • Replace Checkit sensor probe
    Source: scribd.com
    Emerson Climate Technologies / CPC · E2 RX/BX/CX, Site Supervisor, ESR8, ParaSync
    E2-CHECKIT-ALARM , Checkit Sensor Is Alarming
    Warning

    Checkit sensor on Suction Group recording high temperature

    Likely Causes
    • Refrigerant loss on that circuit
    • EEV stuck closed
    • High ambient reducing capacity
    First Checks
    • Inspect refrigeration on associated circuit
    • Check EEV operation
    • Pull refrigerant charge
    Source: scribd.com
    Page 1 of 13